A string is panels wired in series, and series wiring adds voltages while the current stays at one panel's level. Work out a string's working voltage, its open-circuit voltage, and the cold-morning voltage that the whole design must respect, from data sheet figures.
| String length | Working voltage | Voc at 25 C | Voc at -10 C |
|---|---|---|---|
| 6 panels | 208 V | 249 V | 273 V |
| 8 panels | 277 V | 332 V | 363 V |
| 10 panels | 346 V | 415 V | 454 V |
| 12 panels | 415 V | 498 V | 545 V |
| 14 panels | 484 V | 581 V | 636 V |
| 16 panels | 554 V | 664 V | 727 V |
Series strings add voltage and keep one panel's current; parallel strings do the opposite. The cold Voc row is the design-critical one: panel voltage climbs as temperature falls, and the highest voltage the inverter ever sees arrives on a frosty morning before the array warms up. Designers hold that figure below the inverter's data sheet maximum with a margin; the size of the margin is a design decision for your installer, and the string sizing tool checks string length against an inverter window you enter.
A longer string of 14 of the same panels, designed for a colder minus 15 degree morning:
String working voltage is panels per string times Vmp; open-circuit voltage is the count times Voc. Both are laboratory-temperature figures. The temperature correction then scales Voc by its coefficient for every degree between 25 and your coldest expected cell temperature: at minus 10 degrees with a 0.27 percent coefficient, each panel's Voc rises by about 9.5 percent.
Current behaves the other way: it is set by one panel, barely moves with string length, and rises only slightly with light and temperature. That asymmetry is why string design is mostly a voltage exercise, and why cable and protection sizing key off Isc rather than Imp.
The semiconductor's band gap widens as it cools, raising the voltage each cell produces. It is the same physics, run backwards, as the power loss on hot days, and it is entirely predictable from the data sheet coefficient.
At best the inverter refuses to start or shuts down; at worst, sustained overvoltage damages it. This is a hard data sheet limit, which is why the cold calculation, not the 25 degree one, decides the maximum string length.
Divide your inverter's maximum input voltage by the cold Voc per panel from this page, and round down, then check the working voltage still lands inside the inverter's MPPT range on hot days. The string sizing tool does both checks against figures you enter.
No. Longer strings at higher voltage actually lose slightly less in cables for the same power, since loss follows current. The limits on string length are the inverter's voltage window, not efficiency.
String Sizing Calculator · MPPT Sizing Calculator · Inverter Sizing Calculator · Panel Temperature (NOCT) Output